Type CA – Non-verifiable disconnector with different pressure zones

A non-verifiable mechanical backflow prevention device which provides disconnection by venting the intermediate pressure zone of the device to the atmosphere when the difference of pressure between the intermediate zone and the upstream zone is not greater than 10% of the upstream pressure. 

Maximum permissible fluid category against which a Type CA device is accepted as adequate backflow protection:

Backflow by back pressure: fluid category 3

Backflow by back siphonage: fluid category 3

Note: relief ports from Type CA backflow prevention devices shall terminate with an air gap, the dimension of which should satisfy a Type AA air gap. 

Interpretation given in Regulators’ Backflow Specification - backflow prevention arrangements and devices: backflow prevention arrangements

We use cookies to give you the best possible experience with Water Regs UK. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.