Type DC – Pipe interrupter with permanent atmospheric vent

A non-mechanical backflow prevention device with a permanent unrestricted air inlet, the device being installed so that the flow of water is in a vertical downward direction.

Maximum permissible fluid category against which a Type DC arrangement is accepted as adequate backflow protection:

Backflow by back pressure:  not acceptable for protection against back pressure from any fluid category 

Backflow by back siphonage: fluid category 5

Note: arrangements incorporating Type DC devices shall have no control valves on the outlet of the device, they shall be fitted not less than 300mm above the spillover level of a WC pan, or 150mm above the sparge pipe outlet of a urinal, and discharge vertically downwards.  

Interpretation given in Regulators’ Backflow Specification - backflow prevention arrangements and devices: backflow prevention arrangements

 

We use cookies to give you the best possible experience with Water Regs UK. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.