Type HUK1 backflow protection


A hose union tap incorporating a double check valve either at the inlet or out outlet provides a form of backflow protection called a Type HUK1 but can only be lawfully used if installed prior to  1st July 1999.

As these taps only provide fluid category 3 back pressure and back siphonage backflow protection, they are typically found in domestic properties. As check valves used outdoors can be prone to freezing and subsequent failure, should such a tap needed to be replaced a like for like product could be used but ideally it should be changed for a standard hose union taps and the double check valve relocated inside the property and protected from freezing.

In premises built after 1st July 1999 if a double check valve is to be used as point of use backflow protection for a hose union tap categorised as a fluid category 3 risk, this must be installed inside the property and if required protected from freezing.





We use cookies to give you the best possible experience with Water Regs UK. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.